TOXFREE MARINE PLUS XTCuZ1-K (AS+) with bedding
The Toxfree Marine Plus XTCuZ1-K (AS+) is specially designed to transmit electric power in the presence of fire, assuring electric supply to emergency circuits, like signalling lights, smoke extractors, acoustic alarms, water pumps, etc. In case of fire, it does not emit toxic or corrosive gases, thereby protecting public health and avoiding any possible damage to electronic equipment.
TOXFREE MARINE PLUS XTCuZ1-K (AS+) cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
IEC 60092-353
Approvals
- DNV-GL ABS
- BUREAU VERITAS
- LLOYD’S REGISTER CE
- RoHS
Thermal performance
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed installations).
- Lowest installation temperature: -15ºC.
Fire performance
- Flame non-propagation according to IEC 60332-1.
- Fire non-propagation according to IEC 60332-3-22.
- Fire resistant according to IEC 60331-21 (90 minutes at 750ºC).
- LSZH (Low Smoke Zero Halogen) according to IEC 60754-1.
- Low smoke emission according to IEC 61034: light transmittance > 60%.
- Low corrosive gases emission according to IEC 60754-2.
Mechanical performance
- Minimum bending radius: x6 cable diameter.
- Impact resistance: AG3 High severity.
Chemical performance
- Chemical & Oil resistance: Acceptable.
- UV resistant according to EN 50618.
Water performance
Water resistance: AD6 waves.
Other
- Meter by meter marking.
- Ripcord. Electric fields resistant.
Installation conditions
- Open Air.
- In conduit.
- On a bulkhead.
Applications
- Marine use.
- Public places.
TOXFREE MARINE PLUS XTCuZ1-K (AS+) cable design
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228.
Insulation
- Mica Tape + Cross linked polyethylene type XLPE 90ºC according to IEC 60092-360.
- The standard identification is the following:
- 1x Natural
- 2 x Blue + Brown
- 3 x Brown + Black + Grey
- 4 x Brown + Black + Grey + Blue
- 5 or more conductors: black numbered
- Other colors available on request.
Armour
Coverage of 100% composed by aluminium-polyester tape and a tinned copper braid.
Outer sheath
LSHF thermoplastic polyolefin outer sheath SHF1 type. acording to IEC 60092-360. Orange color, non-toxic, fire retardant and fire resistant.