TOXFREE-PLUS-diagram

TOXFREE PLUS 331 ZH RZ1-K (AS+)

TOXFREE Plus 331 ZH RZ1-K (AS+) is a fire resistant cable, specially designed to ensure the power supply to emergency circuits in the event of fire. During a fire you need critical circuits to work for life safety (signaling lights, fume extractors, acustic alarms, water pumps, etc) and a secure plant shutdown.

TOXFREE PLUS 331 ZH RZ1-K (AS+) cable performance

Electrical performance

LOW VOLTAGE 0,6/1kV

Standard

IEC 60502-1

Approvals

CE/ RoHS

CPR Construction Products Regulations B2ca-s1a, d1, a1 (according to cross-section) or Cca-s1b,d1,a1 (according to cross-section).

Thermal performance

  • Maximum conductor temperature: 90ºC.
  • Maximum short-circuit temperature: 250ºC (max. 5 s).
  • Minimum service temperature: -40ºC (fixed and protected installations).
  • Minimum installation and handling temperature: -0ºC.

Mechanical performance

  • Minimum bending radius: x5 cable diameter.
  • Impact resistance: AG2 Medium severity.

Chemical performance

  • Chemical & Oil resistance: Acceptable.
  • UV Resistant according to EN 50618.

Water performance

Water resistance: AD5 Jets.

Fire performance

  • Flame non-propagation based on EN 60332-1 and IEC 60332-1.
  • Fire non-propagation based on EN 60332-3, IEC 60332-3 and EN 50399.
  • Fire resistant: (PH120) mínimum 120 minutes at 840ºC: Based on EN 50200 and IEC 60331-2 for Ø cable ≤ 20 mm.
  • Based on EN 50362 and IEC 60331-1 for Ø cable > 20 mm. 180’ at 950ºC (cat C) category C,W & Z based on BS6387.
  • Fire resistant 180’ at 950ºC (cat C) category C,W & Z based on BS6387 (300/500V).
  • LSHF (Low Smoke Halogen Free) based on  EN 60754-1 and IEC 60754-1.
  • Low smoke emission based on EN 61034 and IEC 61034: Light transmittance > 60%
  • Low corrosive gases emission based on EN 60754-2 and IEC 60754-2.

Other

Meter by meter marking.

Installation conditions

  • Open Air.
  • Buried.
  • In conduit.

Applications

  • Industrial use.
  • Emergency circuits
  • Public places.

TOXFREE PLUS 331 ZH RZ1-K (AS+) cable design

Conductor

Electrolytic annealed copper, class 5 (flexible), based on EN 60228 and IEC 60228.

Insulation

  • Mica tape + Cross-linked polyethylene type DIX-3 according to HD 603.
  • The standard identification of insulated conductors according to HD 308 is the following:
  • 1 x Natural
  • 2 x Blue + Brown
  • 3 x Blue + Brown + Grey
  • 3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
  • 4 x Brown + Black + Grey + Blue
  • 5 G Brown + Black + Grey + Green/yellow + Blue

Outer sheath

Low Smoke Halogen Free (LSHF) polyolefin. Orange color, non-toxic, fire retardant and fire resistant.